BXM-3/K32燃料車間防爆照明配電箱適用范圍
◆爆炸性氣體環境:1區、2區
◆場所中危險氣體或蒸氣:IIA、IIB、IIC
◆溫度組別:T1~T6
◆戶內、戶外
◆Explosive gas atmospheres:Zone 1&2
◆Dangerous gases or vapors zone:IIA、IIB、IIC
◆Temperature Classes:T1~T6
◆Indoor and outdoor
BXM-3/K32燃料車間防爆照明配電箱產品特點
◆鑄鋁合金或鋼板焊接外殼,表面噴塑
◆內裝C65、NC100H、DZ47等小型斷路器
◆具有過載、短路保護功能
◆輸入:3P N PE,輸出:3P N PE或1P N PE
◆可根據用戶要求特制
◆可鋼管或電纜布線
Features
◆Enclosure is made of casting aluminum alloy,surface is sprayed with plastic
◆Built-in small breaker such as C65N(H)-C、C65N(H)-D、NC100Hetc
◆With overload and short circuit protect function
◆C65N(H)-C is proferred for light power distribution system and C65N(H)-1 for power distribution system
◆Inlet,Outlet compartment and component component are independent from each other
◆Input,3P N PE,out:3P N PE or 1P N PE
◆For user's requirement,it could be special one
◆Wiring with conduit or cable.For cable,it should be fitted with explosion protected cable seal gland
1、防爆標志:Exde IIB T4、Exde IIC T4
2、防護等級:IP55、IP65
3、額定電壓:220V、380V
4、極數:IP+N+PE,3P+N
5、額定電流:16A、32A
6、進線口螺紋:G2”~G3”
7、出線口螺紋:G1 1/2”
8、布線方式:電纜布線
9、執行標準:GB3836-2000,IEC60079
適用范圍:
1.1爆炸性氣體環境危險區域的劃分
不同的國家和地區,按各自的標準劃分爆炸危險區域。我國根據爆炸性氣體混合物出現的頻繁程度和持續時間,將爆炸性氣體環境分為O區、1區和2區。(與IEC電工委員會*)
0區:連續出現或*出現爆炸性氣體混合物的環境。
1區:在正常運行時可能出現爆炸性氣體混合物的環境。
2區:在正常運行時不可能出現爆炸性氣體混合物的環境或即使出現也僅是短時存在的爆炸性氣體混合物的環境。
0區一般只存在于密封的容器,貯罐等內部氣體空間,在實際設計過程中1區也很少存在,大多數情況屬于2區。
BXX51防爆檢修電源箱技術參數
■ 執行標準:GB3836.1-2000、GB3836.2-2000、GB3836.3-2000、IEC60079
■ 防爆標志: ExedⅡCT6 *ExedⅡBT6
■ 額定電壓:AC380/220V/50Hz
■ 主回路額定電流:60A-250A
■ 防護等級:IP55
■ 防腐等級:WF1
■ 進線口規格:G2"-G3"
■ 出線口規格:G11/2" BXX51系列防爆動力檢修箱產品特點
■ 殼體采用鋁合金壓鑄成型,表面高壓靜電噴塑;
■ 主腔內裝塑殼式斷路器;
■ 電纜或鋼管布線;
■ 可根據用戶要求特制
適用范圍
◆適用于1區、2區危險場地。
◆適用于ⅡA、ⅡB、ⅡC類,溫度組別為T1-T6的性氣體環境
溫馨提示:
定貨時應嚴格按型號含義詳細注明產品各項參數,及防爆標志和所需數量等;
如有總開關,并注明總開關的電流大小或提供圖紙;
如有特殊要求,請另行注明
防爆插座箱BXX52-2/16K
防爆插座箱BXX52-3/32K
防爆插座箱BXX52-4/60K
防爆插座箱BXX52-6/100K
防爆檢修箱BXX52-8/63K