SM 1222 數字量輸出信號模塊將 SIMATIC S7-1200 的內部信號電平轉換為過程所需的外部信號電平。
Technical Specifications
Order number
6ES7222-1BF32-0XB0
6ES7222-1BH32-0XB0
6ES7222-1HF32-0XB0
6ES7222-1XF32-0XB0
DIGITAL OUTPUT SM1222, 8 DO, 24V DC
DIGITAL OUTPUT SM1222, 16 DO, 24V DC
DIGITAL OUTPUT SM 1222, 8 DO, RELAY
DIGITAL OUTPUT SM1222, 16 DO, RELAY
DIGITAL OUTPUT SM 1222, 8 DO, CHANGEOVER
Product type designation
Supply voltage
permissible range, lower limit (DC)
20.4 V
20.4 V
20.4 V
20.4 V
20.4 V
permissible range, upper limit (DC)
28.8 V
28.8 V
28.8 V
28.8 V
28.8 V
Input current
from backplane bus 5 V DC, max.
120 mA
140 mA
120 mA
135 mA
140 mA
Digital inputs
● from load voltage L+ (without load), max.
11 mA/relay coil
11 mA/relay coil
16.7 mA/relay coil
Power losses
Power loss, typ.
1.5 W
2.5 W
4.5 W
8.5 W
5 W
Digital inputs
Number of digital inputs
0
0
0
0
0
Digital outputs
Number of digital outputs
8
16
8
16
8
● In groups of
1
1
2
1
1
short-circuit protection
No; to be provided externally
No; to be provided externally
No; to be provided externally
No; to be provided externally
No; to be provided externally
Limitation of inductive shutdown voltage to
typ. (L+) -48 V
typ. (L+) -48 V
Switching capacity of the outputs
● with resistive load, max.
0.5 A
0.5 A
2 A
2 A
2 A
● on lamp load, max.
5 W
5 W
30 W with DC, 200 W with AC
30 W with DC, 200 W with AC
30 W with DC, 200 W with AC
Output voltage
● Rated value (DC)
24 V
24 V
5 V DC to 30 V DC
5 V DC to 30 V DC
5 V DC to 30 V DC
● Rated value (AC)
5 V AC to 250 V AC
5 V AC to 250 V AC
5 V AC to 250 V AC
● for signal "0", max.
0.1 V; with 10 kOhm load
0.1 V; with 10 kOhm load
● for signal "1", min.
20 V DC
20 V DC
Output current
● for signal "1" rated value
0.5 A
0.5 A
● for signal "1" permissible range, max.
2 A
2 A
2 A
● for signal "0" residual current, max.
10 ?A
10 ?A
Output delay with resistive load
● "0" to "1", max.
50 ?s
50 ?s
10 ms
10 ms
10 ms
● "1" to "0", max.
200 ?s
200 ?s
10 ms
10 ms
10 ms
Aggregate current of outputs (per group)
horizontal installation
— up to 50 °C, max.
4 A; Current per mass
8 A; Current per mass
10 A; Current per mass
10 A; Current per mass
2 A; Current per mass
Relay outputs
● Number of relay outputs
8
16
8
● Rated input voltage of relay coil L+ (DC)
24 V
24 V
24 V
● Number of operating cycles, max.
mechanically 10 million, at rated load voltage 100,000
mechanically 10 million, at rated load voltage 100,000
mechanically 10 million, at rated load voltage 100,000
Switching capacity of contacts
— with inductive load, max.
0.5 A
0.5 A
2 A
2 A
2 A
— on lamp load, max.
5 W
5 W
30 W with DC, 200 W with AC
30 W with DC, 200 W with AC
30 W with DC, 200 W with AC
— with resistive load, max.
0.5 A
0.5 A
2 A
2 A
2 A
Cable length
● shielded, max.
500 m
500 m
500 m
500 m
500 m
● Unshielded, max.
150 m
150 m
150 m
150 m
150 m
Interrupts/diagnostics/status information
Alarms
● Alarms
Yes
Yes
Yes
Yes
Yes
● Diagnostic alarm
Yes
Yes
Yes
Yes
Yes
Diagnostic messages
● Diagnostic functions
Yes
Yes
Yes
Yes
Yes
● Monitoring the supply voltage
Yes
Yes
Yes
Yes
Diagnostics indication LED
● For status of the outputs
Yes
Yes
Yes
Yes
Yes
● for maintenance
Yes
Yes
Yes
Yes
Yes
● Status indicator digital output (green)
Yes
Yes
Yes
Yes
Yes
Potential separation digital outputs
● between the channels
Relays
Relays
Relays
● between the channels, in groups of
1
1
2
4
1
● between the channels and the backplane bus
500 V AC
500 V AC
1500 V AC for 1 minute
1500 V AC for 1 minute
1500 V AC for 1 minute
Permissible potential difference
between different circuits
750 V AC for 1 minute
750 V AC for 1 minute
750 V AC for 1 minute
Degree and class of protection
Degree of protection to EN 60529
● IP20
Yes
Yes
Yes
Yes
Yes
Standards, approvals, certificates
CE mark
Yes
Yes
Yes
Yes
Yes
CSA approval
Yes
Yes
Yes
Yes
Yes
cULus
Yes
Yes
Yes
Yes
Yes
FM approval
Yes
Yes
Yes
Yes
Yes
RCM (formerly C-TICK)
Yes
Yes
Yes
Yes
Yes
Marine approval
● Marine approval
Yes
Yes
Yes
Yes
Yes
Ambient conditions
Free fall
● Drop height, max. (in packaging)
0.3 m; five times, in dispatch package
0.3 m; five times, in dispatch package
0.3 m; five times, in dispatch package
0.3 m; five times, in dispatch package
0.3 m; five times, in dispatch package
Ambient temperature in operation
● Permissible temperature range
-20 °C to +60 °C horizontal mounting, -20 °C to 50 °C vertical mounting, 95% humidity, non-condensing
-20 °C to +60 °C horizontal mounting, -20 °C to 50 °C vertical mounting, 95% humidity, non-condensing
-20 °C to +60 °C horizontal mounting, -20 °C to 50 °C vertical mounting, 95% humidity, non-condensing
-20 °C to +60 °C horizontal mounting, -20 °C to 50 °C vertical mounting, 95% humidity, non-condensing
-20 °C to +60 °C horizontal mounting, -20 °C to 50 °C vertical mounting, 95% humidity, non-condensing
● Min.
-20 °C
-20 °C
-20 °C
-20 °C
-20 °C
● max.
60 °C
60 °C
60 °C
60 °C; Number of simultaneously activated outputs: 8 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 16 at 55 °C horizontal or 45 °C vertical
60 °C; Number of simultaneously activated outputs: 4 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 8 at 55 °C horizontal or 45 °C vertical
● Permissible temperature change
5°C to 55°C, 3°C / minute
5°C to 55°C, 3°C / minute
5°C to 55°C, 3°C / minute
5°C to 55°C, 3°C / minute
5°C to 55°C, 3°C / minute
Ambient temperature during storage/transportation
● Min.
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
● max.
70 °C
70 °C
70 °C
70 °C
70 °C
Air pressure acc. to IEC 60068-2-13
● Storage/transport, min.
660 hPa
660 hPa
660 hPa
660 hPa
660 hPa
● Storage/transport, max.
1 080 hPa
1 080 hPa
1 080 hPa
1 080 hPa
1 080 hPa
Relative humidity
● Permissible range (without condensation) at 25 °C