DCS系統由硬件和軟件組成。DCS系統的硬件安裝包括盤、柜、機的安裝和它們之間的連線,系統工作接地,電源及基本控制部分的安裝,接地與隔離。

DCS系統安裝的外部條件

 

1、 控制室和操作室應具備使用條件:

在安裝前,控制室和操作室的土建、安裝、電氣、裝修工程全部完工,室內裝飾符合設計要求,空調機啟用,并配有吸塵器;

其環境溫度、濕度、照明度及空氣的凈化程度符合DCS系統運行條件才可開箱安裝。

2、 對安裝人員的要求:

安裝人員保持清潔,到控制室或操作室工作換上干凈的拖鞋,已防灰塵進入DCS系統裝置內;

要盡量避免靜電感應對系統元器件的影響,調試時,不穿化纖等容易產生靜電的織物。

機、柜、盤運輸與安裝

 

  • 機、柜、盤要求整體運輸到控制室,安裝前拆箱。

  • DCS系統硬件包裝箱在運輸、開箱、搬運時小心,防止傾倒和產生強烈振動,以免造成意外損失。

  • 開箱時要有設備供應部門人員和接、保、檢部門人員在場共同檢查外觀質量、設備內部卡件接線的缺陷、系統隨機帶來的文件、資料等,并做好記錄,簽字確認。

  • DCS系統控制室通常有500mm左右的防靜電、防潮地板,因此要考慮好底座高度,并保證其穩定性和強度。

英文資料

The DCS system consists of hardware and software. The hardware installation of the DCS system includes the installation of panels, cabinets, and machines, as well as the wiring between them, system working grounding, installation of power supply and basic control parts, safety grounding and isolation.

External conditions for DCS system installation

1. The control room and operation room should have the following conditions for use:

Before installation, the civil, installation, electrical, and decoration works of the control room and operation room must be completed, and the indoor decoration must meet the design requirements. The air conditioning unit must be activated and equipped with a vacuum cleaner;

Only when the ambient temperature, humidity, lighting level, and air purification level meet the operating conditions of the DCS system, can they be unpacked for installation.

2. Requirements for installation personnel:

The installation personnel must maintain cleanliness, and when working in the control room or operation room, they must wear clean specialized slippers to prevent dust from entering the DCS system device;

Avoid the impact of Electrostatic induction on system components as much as possible. During debugging, do not wear chemical fibers and other fabrics that are prone to static electricity.

Transportation and installation of machines, cabinets, and panels

The machine, cabinet, and panel are required to be transported as a whole to the control room and unpacked before installation.

The DCS system hardware packaging box must be carefully transported, unpacked, and handled to prevent tipping and strong vibration, in order to avoid accidental losses.

When opening the box, personnel from the equipment supply department, as well as personnel from the reception, maintenance, and inspection departments, should be present to jointly inspect the appearance quality, defects in the internal card wiring of the equipment, documents and materials randomly brought by the system, and make records and sign for confirmation.

The DCS system control room usually has an anti-static and moisture-proof floor of about 500mm, so it is necessary to consider the height of the base and ensure its stability and strength.

免責聲明:

AMIKON我們銷售新產品和停產產品,獨立渠道購買此類特色產品。阿米控不是本網站特色產品的授權分銷商、經銷商或代表。本網站上使用的所有產品名稱/產品圖片、商標、品牌和徽標均為其各自所有者的財產。帶有這些名稱,圖片、商標、品牌和徽標的產品描述、描寫或銷售僅用于識別目的,并不表示與任何權利持有人有任何關聯或授權。

GEIC694ALG392 本特利136711-02
GEIC694ALG233本特利136711-01
GEIC694ALG223 本特利136294-01
GEIC694ALG223BENTLY NEVADA136188-02
GEIC693PWR331本特利136188-02
GEIC693PWR330本特利135813-01
GEIC693PWR322本特利135137-01
GEIC693PWR321BENTLY NEVADA135137-01
GEIC693PTM101本特利133819-02
GEIC693PCM301本特利133819-01